Beckhoff ADS (experimental)
This protocol is experimental. It has been tested on CX7000 and CX8190 (TwinCAT 3) and CX1020 (TwinCAT 2); behaviour on other controllers may differ.
This input reads variables from Beckhoff PLCs over ADS by symbol name, either as change notifications pushed by the PLC or as interval polling. It works with TwinCAT 2 and TwinCAT 3, runs from a virtual machine or a container, and can register its own route on the PLC.
This input reads symbols only: named variables such as GVL_ProcessData.nMasterCycleCounter. Direct addresses (%MB100) are not supported.
Where to go
Getting first values out of a PLC, step by step
ADS, AMS NetIDs and routes; read this once and the settings explain themselves
Every setting, with complete examples
How to address symbols, and what each message carries
Containers, VPNs, NAT, and creating routes by hand
Symptoms, causes, and what the log lines mean
Prerequisites
Have these ready before you start. Everything else has a working default.
PLC address
The IP address of the PLC, reachable from wherever this runs
ping <plc-ip>
ADS port open
TCP 48898 to the PLC
nc -z -w3 <plc-ip> 48898
Route port open
UDP 48899, only if the plugin should register its own route
Blocked UDP means creating the route by hand instead
PLC credentials
An administrator user on the PLC, only for automatic route registration
The same login you would use in TwinCAT to add a route
This client's address
The address the PLC will see this client as, needed for hostIP
Usually the VM's IP on the PLC network. Behind a container boundary, VPN or NAT it is something else: see Networking
Symbol names
The full name of each variable, e.g. GVL_ProcessData.nMasterCycleCounter
Read them from the PLC project in TwinCAT
A running PLC runtime
The runtime must be in RUN, not CONFIG
A stopped runtime accepts the connection and serves nothing
Two limits worth knowing up front:
Beckhoff recommends no more than 550 notifications per device. Above that, read in fewer, larger pieces (a struct instead of its members) or switch to
readType: interval, which reads with sum commands.A PLC serves one connection per client address. A second client from the same address displaces the first. That second client can be another instance of this input, or an engineering station behind the same NAT gateway.
Last updated