Configuration
This section covers every setting the Beckhoff ADS input accepts, if they are required or not and the default value if not used, together with two complete example configurations that use them.
Settings
targetAddress
Yes
—
IP address (and optional port) of the PLC's ADS gateway, as ip or ip:port. Port defaults to 48898 if omitted
targetAMS
No
discovered
AMS net ID of the target runtime. Left empty, the plugin asks the PLC for its own on connect, so it normally does not need setting. Set it only to pin a specific runtime; a mismatch with what the PLC reports is logged as a warning, not an error
loadSymbols
No
false
Download the PLC's symbol and datatype table on connect. Required to read a struct or array as one value, which arrives as nested JSON. A named member (GVL.stStatus.fValue) resolves without it. The download can cause brief real-time jitter on the PLC, so it is off by default
runtimePort
No
851
AMS port of the PLC runtime. 851 is the first TwinCAT 3 runtime and 801 the first TwinCAT 2 one, so a TwinCAT 2 PLC has to set this. 0 asks the PLC for its TwinCAT version and uses the first runtime of that version. A later runtime (811, 821 on TwinCAT 2; 852, 853 on TwinCAT 3) always has to be set explicitly
hostAMS
No
auto
Host AMS net ID. Usually the IP address + .1.1. Must match a route on the PLC. auto (or empty) derives it from hostIP when that is set, otherwise from the outbound connection's local IP
hostPort
No
0
AMS source port in protocol headers. 0 uses a random port per session (recommended, avoids notification handle conflicts across sessions). Set a fixed value only in firewalled environments with port allow-lists
readType
No
notification
Read type for the symbols. interval polls at intervalTime; notification uses PLC push updates (see Interval vs Notification). Accepted values: notification, interval
maxDelay
No
100ms
Maximum time the PLC batches notifications before sending (e.g. 100ms, 0s). All changes are still delivered; this controls delivery latency vs network efficiency. 0s = send immediately. Only applies when readType is notification
cycleTime
No
100ms
How often the PLC checks the symbol for changes (e.g. 100ms, 10ms, 1s). Lower = more responsive but more PLC CPU. Values faster than the PLC task cycle are clamped to the task cycle. A symbol's first sample arrives at its first check, so a large value also delays startup, see First batch completeness. Only applies when readType is notification
intervalTime
No
1s
Interval time between reads (e.g. 1s, 500ms). Only used when readType is interval
requestTimeout
No
5s
Timeout for individual ADS requests (e.g. 5s, 10s). Increase for slow PLCs or large symbol tables
transmissionMode
No
serverOnChange
Notification transmission mode. Only applies when readType is notification. Accepted values: serverOnChange, serverCycle, serverOnChange2, serverCycle2 (see Transmission modes)
username
No
""
Username for automatic UDP route registration on the PLC. Both username and password must be set to activate registration. Requires UDP port 48899 to be reachable (see Route Registration)
password
No
""
Password for automatic UDP route registration on the PLC
maxReconnectInterval
No
30s
Upper bound on the reconnect backoff, and on the cooldown applied to a connection that keeps flapping. Every reconnect costs the PLC an accepted socket, which the default protects; lower it for a device that resets on a timer anyway and where samples matter more than sockets (see Reconnection). 0s keeps the library default
routeActivationTimeout
No
10s
How long to wait, after registering a route, for the PLC's AMS router to start serving it. The router acknowledges the registration before the entry is necessarily live, and until it is, requests are dropped with no reply. Raise it for a PLC or router under heavy load. 0s keeps the library default
notificationSilenceTimeout
No
10s
How long the plugin's connection heartbeat may be silent before the subscriptions are treated as dead and re-registered. Converted internally into a number of missed beats. Only applies when readType is notification. 0s keeps the library default
heartbeatRecovery
No
immediate
What to do when notification delivery goes silent; see Silent notification delivery. Accepted values: immediate, confirm, rebuild
hostIP
No
auto
IP address the PLC associates with the route. It must be the address the PLC sees this client as, which behind a NATing gateway is not the client's own address. See PLC behind a NATing gateway. Required in Docker bridge networking on TwinCAT 2, where replies are routed via this address (set to Docker host's IP); optional on TwinCAT 3. When hostAMS is auto, the AMS NetID is also derived from this. auto (or empty) detects it from the outbound connection (only correct with host_network or macvlan)
ADS library log verbosity follows the pipeline log level, the top-level logger.level key in config.yaml. There is no separate setting.
Transmission modes
Note:
transmissionModeonly applies whenreadTypeisnotification. When usingreadType: interval, the plugin sends plain ADS Read commands to the PLC at each interval, no notification mechanism is involved, andtransmissionModeis ignored.
The transmissionMode field controls how the PLC's internal notification handler sends updates back to the client. The available modes are:
serverOnChange
4
Default. The PLC checks the value every cycleTime and sends a notification only when it changed. The check runs in the target's default task.
serverCycle
3
The PLC sends the current value every cycleTime, whether or not it changed. Use for a steady stream or a heartbeat.
serverOnChange2
6
OnChangeInContext: the same check, bound to the task that owns the variable instead of the default task, which makes the timing task-synchronous. Falls back to serverOnChange for any symbol whose ContextMask is 0
serverCycle2
5
CyclicInContext: as serverCycle, bound to the task that owns the variable. Falls back to serverCycle for any symbol whose ContextMask is 0
Choosing a mode:
Use
serverOnChange(default) for event-driven data where only changes matterUse
serverCyclefor periodic snapshots regardless of changesThe
2variants are safe to set on any PLC, because a symbol with ContextMask 0 falls back to the v1 equivalent. They only change behavior for variables local to a PROGRAM POU in a multi-task project; a GVL variable or a single-task project always has ContextMask 0. Beckhoff describes these asCyclicInContextandOnChangeInContextand advises against them in the default case
Full example: TwinCAT 3
All fields with TC3 defaults and comments:
Full example: TwinCAT 2
All fields with TC2 differences highlighted:
Supported hardware
Verified on the following controllers:
CX7000 (TC/RTOS, ARMv7)
3.1.4026
851
CX8190
3.1.4024
851
CX1020
2.10.1320, 2.10.1341, 2.11.2234
801
Each device reports its own model, TwinCAT version and NetID over UDP 48899 before any route exists. That is why targetAMS can be left empty, and what runtimePort: 0 uses to pick the first runtime of the reported version.
TwinCAT 3 (4024 and 4026)
Notifications from a Docker container with bridge networking (no
host_network, no published ports)Automatic UDP route registration from Docker bridge networking
Static route with explicit
hostAMSand no route registrationReconnection after network loss, with automatic notification re-subscribe and symbol reload
Sum/batch commands for read, add notification, and delete notification
cycleTimeverification: 50ms, 200ms and 1000ms intervals match the configured valuesDeterministic value verification against the PLC's own cycle-counter formulas
Recovery from a route whose
Addressthe PLC could not reach
TwinCAT 2 (2.10 and 2.11)
Read batches, notifications, and a range of
cycleTime/maxDelaycombinationsDatatypes: BOOL, SINT, INT, DINT, UDINT, REAL, LREAL, STRING, TIME, DATE, DT, TOD, enums, structs and arrays
Automatic fallback from sum commands to individual calls, and from
SumReadEx2toSumReadExAutomatic fallback from v2 transmission modes to v1
Reconnection after network loss with automatic notification re-subscribe
cycleTimeverification and deterministic value verificationTC2 symbol naming: GVL globals with a leading dot, program locals in uppercase
Migrating from the community plugin
This input replaces the community-supported ads plugin. The input name is unchanged, so an existing configuration keeps loading, but several field names changed, and a config using the old ones fails to start:
targetIP + targetPort
targetAddress, as ip or ip:port
routeUsername
username
routePassword
password
routeHostAddress
hostIP
logLevel
removed; the pipeline's logger.level applies
symbols
removed; use unifiedAddress
targetAMS
unchanged, and now optional: left empty, the plugin asks the PLC for its NetID
runtimePort
unchanged, and still 851 by default, so a TwinCAT 2 PLC still needs 801
hostAMS, hostPort, readType, transmissionMode, cycleTime, maxDelay, intervalTime, loadSymbols
unchanged
Metadata field names changed too: symbol_name is now ads_symbol_name, so a tag_processor carrying msg.meta.tag_name = msg.meta.symbol_name needs updating. See Symbols and metadata for the full set.