How it works

This section covers the background that makes the settings on the other pages understandable. It explains how ADS addresses a device, how the PLC decides whether to accept this client, and what the timing options control. None of it is required reading to get data flowing — the Quick start is enough for that.

How ADS works

Four ideas cover almost everything you need to configure this input.

A router, not a device. Every TwinCAT system runs an AMS router, and you always talk to the router rather than to the PLC program directly. It forwards each request to one of the devices behind it (the PLC runtime, the I/O layer, the logger), selected by a port number. 851 is the first PLC runtime on TwinCAT 3, 801 on TwinCAT 2.

Two addresses, not one. The IP address gets you to the router; an AMS NetID (six numbers, usually written like an IP with .1.1 appended) identifies the system at either end. Your request carries both your own NetID and the target's. The plugin asks the PLC for its NetID on connect, so normally only the IP needs configuring.

A route authorizes you. The PLC answers only clients it has a route for: an entry pairing your NetID with the address it expects you to come from. Routes live on the PLC, survive reboots, and can be created by the plugin itself (username + password) or by hand in TwinCAT. If a request arrives with no matching route, the connection is accepted and then ignored. That is the most common cause of an input that looks connected but reads nothing. See How a route is matched.

One connection, two ways to read. Everything runs over a single outbound TCP connection to port 48898, and normally no inbound port is needed. On that connection you either poll (readType: interval) or subscribe and let the PLC push values when they change (readType: notification, the default). Use interval when the symbol list is long enough to pass the PLC's notification limit, and notification when values change less often than you would otherwise poll. Symbols are addressed by name, so GVL_ProcessData.nMasterCycleCounter is all you need; the PLC resolves it to a handle.

Getting the PLC to accept this client

A route has to exist on the PLC before any data flows, and there are three ways to create one: the TwinCAT Connection Manager on a Windows host, a static route added in the TwinCAT System Manager or XAE, or automatic registration by the plugin itself from username and password. Automatic registration also needs hostIP, because that becomes the address stored in the route. Networking has the procedure for each, and How a route is matched explains what the PLC checks.

How a route is matched

An AMS route pairs an AMS NetID with an address, and the runtime uses both. The NetID selects the route, and it must equal the source NetID the client advertises. The address is checked against the source IP the runtime observes. If they disagree, the TCP connection stays up and the requests are silently dropped: no error, no reply. Replies to requests that do pass come back over the connection the client opened.

NetId only has to match what the client advertises (hostAMS) and need not resemble the address. Address must equal the source IP the PLC observes. Note observes, not can reach.

Replies and notifications normally arrive over the connection the client opened, so the input works from a Docker container with no inbound path and no listening ports.

A device can instead answer only on a connection it opens back to the client on TCP 48898. The plugin accepts that connection and reads the replies from it, so there is nothing to configure. Two things still have to hold: 48898 must be free on the client host, and the PLC must be able to reach it. If the port is already taken, the plugin logs a warning that names it, and that device cannot be read.

Routes are bidirectional by default. Leave that alone: with Unidirectional ticked, the runtime stops accepting ADS calls from the system at the far end of the route, which is this client, so it refuses the plugin's own requests.

A wrong Address produces a session that connects and registers successfully and then fails, usually as repeated request timeouts rather than a connection error.

Automatic registration derives both fields from hostIP (Address = hostIP, NetId = hostIP

  • .1.1). Firmwares differ in what they store when hostIP is left as auto. Some record the source address they observe, others the value the client advertises, so set hostIP explicitly or add the route manually.

Notifications or polling

The interval and notification read types can produce similar-looking results (periodic data), but they work differently under the hood:

  • interval: The client polls the PLC every intervalTime, reading the whole symbol list in one sum command. No PLC notification overhead, and the 550-notification limit does not apply.

  • notification + serverOnChange: The PLC pushes data only when a value changes. After one initial sample at the first check, it sends nothing while the value is unchanged. Counts against the 550-notification limit.

  • notification + serverCycle: The PLC pushes data at every cycleTime interval regardless of changes. Similar result to interval but PLC-driven: more precise timing, with no request/response overhead per cycle. Counts against the 550-notification limit.

Aspect

interval

notification + serverOnChange

notification + serverCycle

Who drives

Client polls

PLC pushes on change

PLC pushes on timer

Network per cycle

Request + response

Push only

Push only

Sends unchanged values

Yes

No, after the initial sample

Yes

Timing precision

Subject to network latency

PLC real-time task

PLC real-time task

PLC notification limit

No limit

550 per device

550 per device

Best for

Large symbol lists, simple setup

Event-driven data (most use cases)

Precise periodic sampling

Choosing cycleTime and maxDelay

cycleTime controls how often the PLC checks the variable:

  • serverCycle mode: PLC sends a notification every cycleTime regardless of value change

  • serverOnChange mode: PLC checks the value every cycleTime and sends a notification only if it changed

maxDelay controls how long the PLC can buffer notifications before sending:

  • The PLC collects notification events and sends them in a batch when maxDelay expires

  • This is a network optimization: fewer packets, multiple notifications bundled in one AMS packet

Practical example, cycleTime: 10ms, maxDelay: 100ms, mode serverOnChange:

  1. PLC checks variable every 10ms

  2. If value changed, queues a notification

  3. Sends queued notifications at most every 100ms (batched)

Edge cases:

  • maxDelay: 0s: send immediately, no batching

  • cycleTime: 0s: check as fast as the PLC task cycle allows

  • maxDelay < cycleTime: effectively no batching (fires before next check)

Think of it as:

  • cycleTime = polling interval (sensor sampling rate)

  • maxDelay = delivery batch window (network efficiency)

Important: If a variable changes faster than cycleTime, intermediate values are missed:

The PLC only samples at cycleTime intervals. Between checks it is blind. This is not a continuous event stream.

For fast-changing values, set cycleTime close to the PLC task cycle time (typically 1–10ms). The trade-off is more CPU load on the PLC and more network traffic. Even at minimum cycleTime, there is no guarantee of capturing every value: if a variable changes twice within one PLC scan cycle, the intermediate value is lost. ADS notifications are polling with push delivery, not event capture.

Which of the four transmission modes applies, and what the 2 variants change, is in Transmission modes.

What to expect from notifications

First batch completeness

When readType: notification, TwinCAT sends an initial sample for every subscribed symbol in every one of the four transmission modes, including for a symbol whose value never changes: the first check has no previous value to compare against, so it always reports.

That initial sample arrives at the first check, one cycleTime after registration (plus maxDelay where the PLC batches), not at registration itself. cycleTime is the interval at which the PLC compares the value, floored by the task cycle, so the wait scales with what you configure:

cycleTime

First sample arrives after

0s

one PLC task cycle (~10ms on a 10ms task)

100ms (default)

~120ms

1s

~1.02s

60s

~60.02s

The plugin waits for these initial samples before returning from Connect, so the first ReadBatch returns a complete batch containing one message per successfully registered symbol, and no separate read or warm-up period is needed to get the current state of all symbols.

The consequence is that a large cycleTime delays startup, because Connect cannot complete before the slowest symbol's first check. With the defaults that is about 0.2s. The wait is bounded at cycleTime + maxDelay + 10s for the slowest configured symbol; if a symbol has still not reported by then, a warning names it and startup continues, and that symbol's data arrives once the PLC does report it.

The connection heartbeat

With readType: notification the plugin subscribes to one extra cyclic notification of its own, on the PLC's symbol-version group. Those beats are the sign that the runtime is still serving notifications. The beat arrives every 2 s by default, carries one byte, and counts as one of the PLC's 550 notifications.

It exists because a runtime restart or a CONFIG toggle can empty the PLC's notification table without dropping the TCP connection, which would otherwise leave the input connected and silent.

notificationSilenceTimeout sets how much silence is tolerated, and is converted into a number of beats: 10 s against a 2 s cycle means five missed beats mark the subscriptions dead. What happens then is heartbeatRecovery, see Silent notification delivery. A PLC that refuses the subscription is logged as a warning and still serves data; only the ability to notice a silent death is lost.

readType: interval has no heartbeat, and needs none: a runtime that stops answering fails the next read.

Partial registration failures

If a symbol fails to register (unknown name, PLC-side ADS error), the plugin:

  • Logs an error through the Benthos logger identifying the symbol and reason

  • Continues with the remaining symbols, so data still flows for every symbol that did register

  • Does not trigger a reconnect for partial failures; only a full failure (zero symbols registered) forces a reconnect

This means a misconfigured symbol name is surfaced immediately in logs without blocking data from the other symbols.

Interval read: empty batches during reconnect

When readType: interval, the first one or two batches after a reconnect may be empty or partial while symbol handles are re-resolved. This is normal, Benthos retries the next poll and subsequent batches are complete. No action is needed; the gap is typically one poll interval (default 1 second).