Networking

This section covers what to configure when network is not a straight path to the PLC, for example running from a Docker container, special network routing, or via a VPN. It also shows how to create a route on the PLC by hand, for the cases where the plugin cannot register one itself.

Where the client runs

Where the client runs decides which address the PLC sees, and that address is what a route has to match. The three cases below cover a container, a virtual machine, and a host on a routed network. This part is written for whoever administers the host and the network path to the PLC.

Containers and Kubernetes

ADS works from inside Docker containers with default bridge networking. You need no host_network and no port forwarding: requests, responses and notifications normally all flow over the single outbound TCP connection the plugin opens to port 48898. One case does need inbound 48898, a device that answers only on a connection it opens back to the client. See How a route is matched.

The only other requirement is that the hostAMS value matches a route registered on the PLC. When running in Docker with bridge networking:

  • hostIP should be set to the Docker host's IP on the PLC network (e.g. 192.168.1.50). auto detects the container's bridge IP, which the PLC cannot match. See How a route is matched.

  • hostAMS can be set explicitly to hostIP + .1.1 (e.g. 192.168.1.50.1.1), or left as auto: when route registration is configured with hostIP, auto will correctly derive the AMS NetID from hostIP instead of the container's bridge IP.

  • A route must exist on the PLC for the hostAMS NetID. This can be added manually in TwinCAT System Manager, or automatically via the username/password config fields.

  • hostPort is optional (default 0 = random per session). It is a logical AMS port used in protocol headers, not a network port.

Option A: Automatic route registration (recommended)

The plugin registers a route on the PLC automatically via UDP before connecting. No manual PLC configuration needed:

input:
  ads:
    targetAddress: "192.168.1.100"
    hostAMS: "auto"                        # derives NetID from hostIP
    hostIP: "192.168.1.50"                 # Docker host IP (required in bridge networking)
    username: "Administrator"              # triggers automatic route registration
    password: "1"
    unifiedAddress:
      - "MAIN.MyVariable"

You can also set hostAMS explicitly if you prefer:

Option B: Static route on PLC

If you prefer not to use automatic registration, add a static route on the PLC via TwinCAT System Manager pointing to the Docker host's IP. Then configure hostAMS to match. No username/password needed:

Option C: host_network or macvlan

When the container has a routable IP on the PLC network, hostAMS: auto works without hostIP:

PLC behind a port-forwarding router

When an IT router maps an external port to the PLC's internal ADS port (for example, external 4233 → internal 48898), set targetAddress to the external IP and port:

AMS NetID routing is independent of IP and port, so it still resolves correctly once the TCP connection is established.

Automatic route registration uses fixed UDP port 48899 and cannot follow a port-forwarded path. Behind NAT or a port-forwarding router, register the route manually on the PLC (via TwinCAT System Manager → Routes) and leave username and password empty.

PLC behind a NATing gateway or subnet router

hostIP becomes the address stored in the PLC's route, and the PLC then compares the source address it observes against its stored routes. Any gateway that rewrites the source (a VPN subnet router doing SNAT, a NATing firewall) makes every client behind it appear as the gateway's own LAN address. hostIP has to be that address, not the client's.

NAT is an IP-layer operation: it rewrites the IP source and leaves the AMS header alone. So the PLC receives a request whose IP source and AMS source disagree, and it answers on the basis of the AMS one.

The route the client registers stores its own address, but the runtime sees the gateway's, so the two disagree and every request is dropped without an answer. That is the whole failure, and it applies to every runtime: reachability of the stored address is irrelevant, only whether it equals what the runtime observes.

Removing the translation fixes it outright. Where it has to stay, hostIP must be the gateway's address, so that what the route stores and what the runtime observes agree.

With hostIP left as the client's own address the input appears to start normally (the route registers, the connection is accepted) and then fails. Which way it fails varies from device to device rather than following the runtime version:

  • it serves data for a while and the PLC then closes the connection

  • it drops shortly after connecting

  • it connects and subscribes, then every request times out

What the cases share is more useful than the differences: the failure arrives after a similar interval each time while the data volume varies, and readType makes no difference. Both point at configuration rather than the network.

Finding the address the PLC sees. No ADS service reports it, so ask something on the PLC's own subnet:

Any HTTP service already running on that subnet works too: make one request from the Benthos host and read its access log.

Or remove the translation. With SNAT disabled the PLC reaches the client at its own address, and hostIP is that address. That needs a return route for the VPN's range on the LAN (for tailscale, 100.64.0.0/10 via the subnet router), unless the subnet router is the LAN's gateway, in which case the return path already passes through it and nothing extra is required.

If the translation has to stay, add the route manually. That is the one way to give the PLC a reply address that differs from the source it observes. See Adding the route manually on the PLC.

PLC connection check

A health check that port-scans the device periodically can break the ADS session, unless the client runs an AMS router of its own. Whatever the check, do not point it at 48898: the TwinCAT router drops the live ADS session every time that port is scanned, which looks like a flaky network but is self-inflicted. 443 is the usual choice, 80 if 443 is closed on the device. The port has to be open or the check never passes, and a web server answering there only proves the device is powered, not that the ADS runtime is running.

Deploying from the UMH Core Management Console adds such a check with the port prefilled; leave it as it is.

Getting a route onto the PLC

Route entries live on the PLC, so this part needs someone who can log in to the device or has its administrator credentials.

Automatic route registration

The plugin can automatically register a route on the PLC using the Beckhoff UDP route protocol (port 48899). This removes the need to manually add routes in TwinCAT System Manager.

Activation: both username and password must be set.

How it works:

  1. The TCP connection to port 48898 is established

  2. The plugin probes the PLC with a lightweight ADS command to check if a route already exists

  3. If the probe succeeds, route registration is skipped (route already present)

  4. If the probe fails, the plugin sends a UDP registration packet to port 48899: "Associate AMS NetID X with IP address Y"

  5. After registration the TCP connection is re-established (some PLCs close connections from previously-unknown NetIDs)

  6. On reconnect after a network loss, the same probe-first logic runs automatically

Parameters:

  • username / password: PLC administrator credentials, same as used in TwinCAT System Manager to add routes

  • hostIP: the address stored in the route, which has to be what the PLC sees this client as. In Docker with bridge networking that is the Docker host's IP; mandatory on TwinCAT 2, which routes replies via this address. auto (or empty) detects it from the outbound connection (only correct with host_network or macvlan)

A registered route stays on the PLC. Removing one is done on the device, not from here: see Create or delete ADS routes manually or the route list in the TwinCAT System Manager.

Network requirements:

  • UDP port 48899 must be reachable on the PLC from the client (for route registration)

  • TCP port 48898 must be reachable on the PLC from the client (outbound, works through any NAT)

Adding the route manually on the PLC

Automatic registration ties Address and NetId together, since both come from hostIP. A manual route does not, which is what makes it the way out when the two must differ: the address the PLC sees the client as, against whatever NetID the client advertises.

Leave username and password empty when the route is managed this way; the plugin then connects without attempting registration.

On a Windows host the TwinCAT Connection Manager can do this for you: scan for the device and add a connection with the PLC's credentials. Everywhere else, add the route on the device.

Beckhoff documents the click paths, and they differ per tool and firmware:

Whichever tool you use, these are the values that matter:

Field
Value

Route name

anything; it only labels the entry

AMS Net ID

must equal what the client advertises: hostAMS, or hostIP + .1.1 when hostAMS is auto

Address

the address the PLC sees the client as; prefer an IP over a host name unless DNS is reliable on the PLC

Transport type

TCP_IP

Static, not temporary

a temporary route is lost on the next restart

The AMS Net ID and the Address are independent: the NetID need not resemble the address, which is exactly what makes a manual route usable behind NAT.

One asymmetry to expect: between two TwinCAT systems a route is created on both ends. You add it on one side and the peer gets its own entry automatically, which is what the Remote Route options in the XAE dialog are for. This plugin is not a TwinCAT system and runs no router, so only the PLC-side entry exists. There is no second route to look for, and Remote Route can be left at None / Server.

On the device itself, routes live in StaticRoutes.xml:

Platform
Path

TwinCAT 3 on Windows

C:\TwinCAT\3.1\Target\StaticRoutes.xml

CX with Windows CE

\Hard Disk\TwinCAT\3.1\Target\StaticRoutes.xml

Editing it directly is another way to add routes with no engineering station attached. Refer to the official documentation Create or delete ADS routes manually:

NetId must match the source NetID the client advertises; Address is the address the PLC holds for that client. The example is the NAT case written out: the address is a gateway on the PLC's own subnet while the NetID is the client's.

Leave the remaining fields as the tooling wrote them. The plugin only ever sets the NetID, route name, computer name and credentials.