Quick start
In this quick start we set up a TwinCAT 3 PLC as a data source in a Benthos pipeline. By the end of this section you will know how to:
Find the symbols you want to read
Write the input configuration
Add a tag processor
Send the values somewhere
Check that values are arriving
Before you start you need:
A Beckhoff PLC reachable from this host
An administrator user on that PLC
The PLC's IP address
You end with a Benthos config file that you run with benthos -c config.yaml. The whole thing takes about 15 minutes.
Step 2 writes a route entry to the PLC, so point this at a PLC you are allowed to configure.
The same five steps work for TwinCAT 2, with different symbol names and a different runtime port. There is a complete TwinCAT 2 example at the end of this page.
1. Find the symbols you want
Open the PLC project in TwinCAT and note the full name of each variable, for example GVL_ProcessData.nMasterCycleCounter. Global variables live under their GVL name; program variables under the program name.
2. Write the input
Warning:
usernameandpasswordbelow make the plugin register a route on the PLC. That writes a persistent entry to the device's route table, which stays until someone removes it on the device. See Getting a route onto the PLC.
targetAMS is discovered from the PLC, so you do not need its AMS NetID. runtimePort is not: it defaults to 851, the first TwinCAT 3 runtime, so a TwinCAT 2 PLC has to set 801. hostIP is the address the PLC will see this client as, which is usually the VM's IP on the PLC network:
3. Add a tag processor
Each message carries the symbol name in ads_symbol_name, which is what the tag name should usually be:
4. Send the values somewhere
stdout prints each value as it arrives, which is enough to prove the PLC side works:
To write to the Unified Namespace instead, swap in the uns output, which needs the embedded Redpanda that ships with UMH Core:
5. Check the values arrive
On the first connect the plugin registers a route on the PLC, subscribes to each symbol, and waits for one value from each before reporting itself connected. In the logs you should see, in order:
Two different registrations appear there. The route registration writes an entry to the PLC's route table and happens once. The notification registration subscribes to each symbol and happens on every connect.
Values then print one per line. The tag_processor step has already set each message's topic to umh.v1.enterprise.site.area.line._historian.<symbol>, which is what the uns output uses as the message key.
If the log stops after Connected to PLC, or symbols register but no values arrive, go to Troubleshooting. The cause is most often a wrong hostIP.
The same config on TwinCAT 2
Global variables carry a leading dot, program variables an uppercase program prefix:
Next
Reading structs, arrays or strings: Symbols and metadata
Running in a container, or across a VPN: Networking
Tuning how often values arrive: Configuration