Quick start

In this quick start we set up a TwinCAT 3 PLC as a data source in a Benthos pipeline. By the end of this section you will know how to:

  1. Find the symbols you want to read

  2. Write the input configuration

  3. Add a tag processor

  4. Send the values somewhere

  5. Check that values are arriving

Before you start you need:

  • A Beckhoff PLC reachable from this host

  • An administrator user on that PLC

  • The PLC's IP address

You end with a Benthos config file that you run with benthos -c config.yaml. The whole thing takes about 15 minutes.

Step 2 writes a route entry to the PLC, so point this at a PLC you are allowed to configure.

The same five steps work for TwinCAT 2, with different symbol names and a different runtime port. There is a complete TwinCAT 2 example at the end of this page.

1. Find the symbols you want

Open the PLC project in TwinCAT and note the full name of each variable, for example GVL_ProcessData.nMasterCycleCounter. Global variables live under their GVL name; program variables under the program name.

2. Write the input

Warning: username and password below make the plugin register a route on the PLC. That writes a persistent entry to the device's route table, which stays until someone removes it on the device. See Getting a route onto the PLC.

targetAMS is discovered from the PLC, so you do not need its AMS NetID. runtimePort is not: it defaults to 851, the first TwinCAT 3 runtime, so a TwinCAT 2 PLC has to set 801. hostIP is the address the PLC will see this client as, which is usually the VM's IP on the PLC network:

3. Add a tag processor

Each message carries the symbol name in ads_symbol_name, which is what the tag name should usually be:

4. Send the values somewhere

stdout prints each value as it arrives, which is enough to prove the PLC side works:

To write to the Unified Namespace instead, swap in the uns output, which needs the embedded Redpanda that ships with UMH Core:

5. Check the values arrive

On the first connect the plugin registers a route on the PLC, subscribes to each symbol, and waits for one value from each before reporting itself connected. In the logs you should see, in order:

Two different registrations appear there. The route registration writes an entry to the PLC's route table and happens once. The notification registration subscribes to each symbol and happens on every connect.

Values then print one per line. The tag_processor step has already set each message's topic to umh.v1.enterprise.site.area.line._historian.<symbol>, which is what the uns output uses as the message key.

If the log stops after Connected to PLC, or symbols register but no values arrive, go to Troubleshooting. The cause is most often a wrong hostIP.

The same config on TwinCAT 2

Global variables carry a leading dot, program variables an uppercase program prefix:

Next