Symbols and metadata

This section explains how to configure a symbol, how its name becomes a topic, and what metadata each message carries once it has been read.

Addressing symbols

Symbols are specified as name[:key=value...]. Each option names the field it sets.

Format
maxDelay
cycleTime

MAIN.var

default

default

MAIN.var:cycleTime=100

default

100

MAIN.var:maxDelay=50

50

default

MAIN.var:maxDelay=50:cycleTime=100

50

100

Rules:

  • Options are key=value; the only keys are maxDelay and cycleTime

  • A bare number is ignored with a warning, and the default is kept

  • Values without a unit are milliseconds; cycleTime=10ms and cycleTime=10 are the same

  • Invalid or omitted values fall back to the plugin-level maxDelay/cycleTime defaults

  • Both options only apply when readType is notification; with interval the plugin polls every intervalTime and per-symbol timing is ignored

Examples:

  • MAIN.MYBOOL: uses plugin-level defaults for both

  • MAIN.MYTRIGGER:maxDelay=0:cycleTime=10: 0ms max delay, 10ms cycle time

  • MAIN.MYSENSOR:cycleTime=10: default max delay, 10ms cycle time

  • .superDuperInt: global variable (TC2, must start with .)

TwinCAT 3 qualifies every symbol with the object that declares it. A global variable is <GVL name>.<variable>, where <GVL name> is whatever the Global Variable List object is called. TwinCAT names a new GVL GVL, so GVL.nCounter is the common case; a list named GVL_ProcessData gives GVL_ProcessData.nCounter. Program variables use the POU name: MAIN.MyVariable, PRG_Machine.nUpdates. There is no fixed GVL_ prefix and no leading dot.

TwinCAT 2 puts globals in one flat namespace with no list name, reached by a leading dot: .nCounter, .stProcessData.fValue. Program variables still carry the POU name and no dot: MAIN.someVar.

Symbol names are case-insensitive, so the PLC accepts any casing. The metadata always carries the casing you configured: TwinCAT 3 returns the original casing, and TwinCAT 2 returns uppercase, which the plugin maps back to what you wrote.

Symbol names in topics

ads_symbol_name becomes the last segment of the UMH topic, where a dot separates levels, so the symbol name has to be rewritten to fit. Array indices keep one separator, a TwinCAT 2 global's leading dot is dropped (it marks the namespace and is not part of the name), and runs of underscores collapse:

PLC symbol

ads_symbol_name

GVL_ProcessData.stMachineStatus.stMotor1.fSpeed

GVL_ProcessData_stMachineStatus_stMotor1_fSpeed

PRG_Diagnostics.astSensorHistory[0].fValue

PRG_Diagnostics_astSensorHistory_0_fValue

.afMeasurements[0] (TC2 global)

afMeasurements_0

.nMasterCycleCounter (TC2 global)

nMasterCycleCounter

_internalVar

_internalVar (a leading underscore may be the PLC's own naming)

The original is always available as ads_symbol_name_original, so a symbol can still be traced back to the PLC. Two symbols can in principle collapse to the same tag name (.a[0] and a variable actually named a_0), so if a program relies on that distinction, use ads_symbol_name_original in the tag_processor instead.

Structs and arrays

A named member reads like any other symbol:

Naming the struct itself returns the whole thing as one message, with the members as nested JSON:

That form needs loadSymbols: true, because the layout comes from the PLC's datatype table. Without it the read fails for the struct and the log says Batch read produced no value for symbol. Reading a member by name needs no table either way.

Metadata outputs

Each symbol produces one message whose payload is the value read from the PLC, so meta("ads_symbol_name") is how a following bloblang processor tells them apart.

Metadata Field
Description

ads_symbol_name

PLC symbol name as one topic segment; see Symbol names in topics

ads_symbol_name_original

The symbol exactly as the PLC names it, dots and brackets intact (e.g. PRG_Diagnostics.astSensorHistory[0].fValue)

ads_unified_address

The unifiedAddress entry this message came from, exactly as configured and including its options (e.g. GVL_ProcessData.nCounter:cycleTime=10ms). Always set. For an entry with no options this equals ads_symbol_name_original

ads_datatype

PLC data type string as reported by the symbol table (e.g. DINT, E_MachineState, REAL). Set after first successful symbol resolution, may be absent on the very first batch after connect.

ads_base_type

Resolved IEC 61131-3 primitive underlying the symbol (e.g. DINT for an INT-aliased enum). Absent when the type does not resolve to a primitive

ads_data_size

Byte length of the symbol as reported by the PLC (e.g. 4 for DINT, 82 for STRING).

ads_tag_type

Value shape of the payload: number, bool, or string. Set for every message so downstream processors can branch on payload type without inspecting ads_datatype/ads_base_type.

timestamp_ms

Unix milliseconds for when the value was captured. For readType: notification, this is the PLC's sample time for that update; for readType: interval, this is the time the plugin performed the read.

Last updated