Troubleshooting
Start from the symptom. Every entry below refers to the plugin's own log output, which Benthos writes to stdout; adding --log.level DEBUG to the benthos -c config.yaml command adds the per-request detail. With no access to those logs, the one check worth making from the PLC side is whether a route exists for this client and what address it holds: see Getting a route onto the PLC.
Connects, registers symbols, no values arrive
hostIP is not the address the PLC sees
Log stops after Connecting to PLC
Wrong address, PLC off, or firewall on 48898
route ... was registered but the PLC did not serve it
Route address or credentials
Values stop but the input keeps running
Notification delivery went silent
Timestamps decades in the past or future
The PLC's own clock, used for notification samples
could not bind the inbound AMS port and every request times out
The device answers on its own connection, and 48898 is taken on this host or blocked inbound
Reading a disconnect
A failed connect logs a hint field naming the likely cause, and the PLC closing the connection is reported as one of two different cases:
the PLC did not accept a TCP connection
Nothing answered on the ADS port
targetAddress, PLC powered, firewall
closed it without serving a single AMS frame
TCP accepted, but the route does not authorize this client
username/password, hostIP (set it explicitly behind NAT or a VPN), another client holding the route from the same host
dropped a connection that was already carrying AMS frames
Transport or device-side reset, not a configuration error
The network path, for VPN or subnet-router flaps. Or another client evicting this one: a Beckhoff AMS router serves one TCP connection per host and closes the older
If those drops arrive after a similar interval each time while the frame counts vary, suspect configuration rather than the network: most often a route whose Address does not match the source the PLC sees. See PLC behind a NATing gateway.
Reconnection
A session that is down is logged at error level: nothing is read while it lasts, and with readType: notification the samples in the gap are gone. Under UMH Core that also holds the bridge out of active until it recovers.
The plugin automatically reconnects when the TCP connection is lost (e.g. network cable unplugged, PLC restart). TCP keepalive is set to probe after 3 s idle, then every 2 s, five times, so a dead connection is declared after about 13 s. On reconnect, the plugin:
Re-establishes the TCP connection, retrying indefinitely on the backoff ramp below
Reloads the symbol table from the PLC
Re-subscribes all notification handles
No manual intervention is needed.
A device that keeps dropping
Reconnect delays ramp 1s → 5s → 15s → 30s and stay at the cap. A connection that drops repeatedly is treated as flapping and gets that cap as a cooldown. A PLC that resets an established connection every few seconds therefore spends most of its time waiting rather than reading. That is deliberate: every reconnect costs the PLC an accepted socket, and the default protects its socket table rather than stream continuity.
Where the samples matter more than the sockets, lower the cap, accepting one more accepted socket on the PLC per reconnect:
The lower tiers are pulled down with it so the ramp stays valid. Check the drop verdict below first: if the drops are the route not being served, a faster reconnect makes it worse.
Silent notification delivery
Notification delivery can stop without the TCP connection dropping, so there is no error and no reconnect. The connection heartbeat is what notices: once its beats stop for notificationSilenceTimeout, the subscriptions count as dead and heartbeatRecovery decides what happens next:
immediate (default)
Re-subscribes at once: one delete plus one add per symbol, in a burst
The PLC answers reliably; fastest recovery from a genuine subscription death
confirm
Waits for a second consecutive silent window, then re-subscribes
The PLC stalls under load. Twice as slow to notice a real death, but one late beat no longer churns every handle
rebuild
Drops the session and reconnects from scratch, re-registering every subscription as part of a fresh connect
The PLC ignores the churn. A device that is not answering times out on both the delete and the add, so every symbol costs two requestTimeout waits (5 s each by default) and never recovers, where a reconnect takes about a second
An input that keeps running while delivering nothing is the failure this protects against: with rebuild the reconnect is visible in the logs, and the plugin reports itself disconnected so the pipeline restarts the input rather than sitting on dead handles.
Why retries slow down
The plugin paces failed connects, and how long it waits depends on why the connect failed:
Ordinary (dial refused, session rejected)
1s, doubling to a 1 min ceiling; a rebooting PLC is still picked up promptly
The PLC will not serve the route
30s, doubling to 5 min
Three consecutive route failures
Route registration is skipped entirely for 5 minutes
The log says which is happening: Waiting before the next connect attempt with the delay, and on the third route failure a warning that registration is being skipped and that hostIP must be the address the PLC sees. Any successful connect clears all of it.
The pacing exists because retrying cannot fix a route the PLC will not serve. Every attempt costs the PLC a route registration and a socket, and enough of them will wedge its route table.
While registration is skipped the plugin also skips the probe, so the clean "route not served" verdict is unavailable until the window expires. That is the trade for not writing to the device's route table.