Siemens S7
This input is tailored for the S7 communication protocol, facilitating a direct connection with S7-300, S7-400, S7-1200, and S7-1500 series PLCs.
For more modern PLCs like the S7-1200 and S7-1500 the following two changes need to be done to use them:
"Optimized block access" must be disabled for the DBs we want to access
In the "Protection" section of the CPU Properties, enable the "Permit access with PUT/GET" checkbox
Configuration
input:
s7comm:
tcpDevice: '192.168.0.1' # IP address of the S7 PLC (optionally with port, e.g., '192.168.0.1:102')
rack: 0 # Rack number of the PLC. Defaults to 0
slot: 1 # Slot number of the PLC. Defaults to 1
timeBetweenReads: 1s # Time waited between two attempts to read data from the device. Defaults to 1s
batchMaxSize: 480 # DEPRECATED: This field never worked correctly because batches were calculated before connecting to the PLC, so the actual negotiated PDU size was unknown. PDU size is now automatically negotiated during connection.
timeout: 10 # Timeout in seconds for connections and requests. Default to 10
disableCPUInfo: false # Set this to true to not fetch CPU information from the PLC
addresses: # List of addresses to read from
- "DB1.DW20" # Accesses a double word at location 20 in data block 1
- "DB1.S30.10" # Accesses a 10-byte string at location 30 in data block 1Configuration Parameters
tcpDevice: IP address or hostname of the Siemens S7 PLC, optionally with port (e.g.,
192.168.0.1:102). If no port is specified, the default S7 port 102 is used.rack: Identifies the physical location of the CPU within the PLC rack.
slot: Identifies the specific CPU slot within the rack.
timeBetweenReads: Time the input waits between two attempts to read data from the device. Takes a duration string with a unit, such as
500ms,1sor2m. The units arens,us,ms,s,mandh. A bare number such as1000is rejected at startup. Defaults to1s. No upper limit is enforced. A negative value or zero is not a usable interval: the input logs a warning and falls back to1s. Low values can overload the PLC.timeout: Timeout duration in seconds for connection attempts and read requests.
disableCPUInfo: Set this to true to not fetch CPU information from the PLC. Should be used when you get the error 'Failed to get CPU information'
addresses: List of PLC memory addresses to read. See Address Format below.
Address Format
Each address tells benthos-umh where to read in the PLC memory and what data type to expect.
For Data Blocks (block number required):
Example: DB1.DW20 — double word at offset 20 in data block 1.
For all other areas (no block number):
Example: PE.W0 — input word at offset 0.
Breaking this down:
area
Memory area in the PLC
DB, MK, PE, PA, C, T
number
Which data block (DB only)
1 in DB1 (Data Block 1)
type
Data type to read
DW, X, S, R, etc.
offset
Byte position within the area
20 in DB1.DW20 (starts at byte 20)
extra
Required for some types only
Bit number for X, string length for S
Only DB (Data Blocks) uses a block number.
Memory Areas
DB
Data Block
Main data storage — most commonly used
DB1.DW20
PE
Process Input
Physical inputs (sensors, switches)
PE.B0
PA
Process Output
Physical outputs (actuators, relays)
PA.W0
MK
Merker (Flags)
Internal boolean/word flags
MK.W0
C
Counter
Hardware counters
C.W0
T
Timer
Hardware timers
T.W0
Data Types
X
Bit
1 bit
bool
Yes — bit number (0–7)
DB1.X5.2
B
Byte
1 byte
uint8
No
DB1.B10
C
Char
1 byte
string (single character)
No
DB1.C10
W
Word
2 bytes
uint16
No
DB1.W20
I
Integer
2 bytes
int16 (signed)
No
DB1.I20
DW
Double Word
4 bytes
uint32
No
DB1.DW100
DI
Double Integer
4 bytes
int32 (signed)
No
DB1.DI100
R
Real
4 bytes
float32
No
DB1.R200
DT
Date/Time
8 bytes
int64 (Unix nanoseconds)
No
DB1.DT0
S
String
variable
string
Yes — max length (≥ 1)
DB1.S30.10
The Extra Parameter
Two data types require the extra parameter (the part after the second .):
Bit (X) — specify which bit (0–7) within the byte:
Bit numbering: 0 is the least significant bit, 7 is the most significant.
String (S) — specify the maximum string length:
The PLC stores strings with a 2-byte header (max length + actual length), so DB1.S30.10 reads 12 bytes starting at offset 30.
All other types must not have an extra parameter.
Examples
Mapping from TIA Portal
When reading addresses from a TIA Portal project, map them like this:
DB1.DBX 5.2
DB1.X5.2
Data bit — drop "DB" prefix from type
DB1.DBB 10
DB1.B10
Data byte
DB1.DBW 20
DB1.W20
Data word
DB1.DBD 100
DB1.DW100
Data double word (unsigned)
DB1.DBD 100
DB1.DI100
Data double word (signed) — same offset, different type
DB1.DBD 200
DB1.R200
Data real (float)
M 0.0
MK.X0.0
Merker bit
MW 10
MK.W10
Merker word
I 0.0
PE.X0.0
Input bit
IW 0
PE.W0
Input word
Q 0.0
PA.X0.0
Output bit
QW 0
PA.W0
Output word
Output
Similar to the OPC UA input, this outputs for each address a single message with the payload being the value that was read. To distinguish messages, you can use meta("s7_address") in a following benthos bloblang processor.
Batching Behavior
Addresses are automatically split into batches based on S7 protocol constraints:
Max 20 items per request: The S7 protocol limits AGReadMulti to 20 addresses per request
PDU size: The request and response must fit within the negotiated PDU size (typically 240-480 bytes depending on the PLC model)
When more than 20 addresses are configured or the combined data exceeds PDU limits, multiple sequential requests are made. This has implications:
Timing: Addresses in different batches are read at slightly different times, resulting in different timestamps
Performance: More batches means more round-trips to the PLC, increasing total read time
Last updated

